Siemens 6RA7086-6KS22 Operating Instructions Manual page 525

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
PNU
Description
11.33 Field reversal
(see also Section 9)
P580
Source for selection of "Direction of rotation reversal using field
*
reversal"
BDS
Selection of binector to control the "Direction of rotation reversal using field
reversal" function
(G200)
0 = binector B0000
1 = binector B0001
etc.
Signal 0: Positive field direction is selected (B0260 = 1, B0261 = 0),
actual speed value is not inverted
Signal 1: Negative field direction is selected (B0260 = 0, B0261 = 1),
actual speed value is inverted
P581
Source for selection of "Braking with field reversal"
*
Selection of binector to control the "Braking with field reversal" function
BDS
0 = binector B0000
1 = binector B0001
(G200)
etc.
Signal change 0→1: Reversal of field direction (causes braking);
P582
Source for selection of "Field reversal"
*
Selection of binector to control "Field reversal" function
BDS
0 = binector B0000
1 = binector B0001
(G200)
etc.
Signal 0: Positive field direction is selected (B0260 = 1, B0261 = 0)
Signal 1: Negative field direction is selected (B0260 = 0, B0261 = 1)
P583
Source for actual speed signal for field reversal logic
*
Selection of connector to be used as actual speed value for the field
(G200)
reversal logic.
0 = binector B0000
1 = binector B0001
etc.
11.34 Input quantities for signals
(see also Section 8, Sheet G187 and G188)
P590
Source for setpoint of "nset = nact signal 1"
*
Setpoint/actual value deviation signal:
Selection of connector to be injected as input quantity "n set " for the
(G187)
setpoint/actual value deviation signal.
0 = connector K0000
1 = connector K0001
etc.
P591
Source for actual value of "n-set = n-act signal 1"
*
Setpoint/actual value deviation signal:
Selection of connector to be injected as input quantity "n act " for the
(G187)
setpoint/actual value deviation signal.
0 = connector K0000
1 = connector K0001
etc.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
When n<n-min is reached, the original field direction is
selected again. The drive switches to state o7.2
Value range
[Unit]
Steps
All binector numbers
1
All binector numbers
1
All binector numbers
[SW 1.9 and later]
1
All connector
numbers
[SW 1.9 and later]
1
All connector
numbers
1
All connector
numbers
1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: None
P052 = 3
FS=167
P051 = 40
Type: L2
off-line
Ind: None
P052 = 3
FS=174
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=167
P051 = 40
Type: L2
Offline
11-61