CEILING DUCT TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS (Refrigerant : R-407C) • This unit is charged with new refrigerant, R-407C. • Be sure to use proper tools for R-407C, when installing the unit. • Please read this instruction sheet completely before installing the product. •...
OUT-LINE OF INSTALLATION 1. The following should be always observed for safety ......3 Installation works Installation Parts Required tools 2. Installation of Indoor, Outdoor unit 1) Selection of the best • • Four Type “A” screws Level location......4 • • Connecting cable Screw driver 2) Indoor unit installation..5...
1. The following should be always observed for safety • Please report to or take consent by the supply authority before connecting to the system. • Be sure to read "THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY" before installing the air conditioner. •...
2. Installation of Indoor, Outdoor Unit 1. Selection of the best location Inspection hole Top view (600X600) 1) Indoor unit (unit: mm) Control box Select location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unit’s weight.
2. Indoor unit installation Installation of Unit Install the unit above the ceiling correctly. CASE 1 POSITION OF SUSPENSION BOLT • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. (Unit:mm) Dimension F (G)
Page 6
• Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling. • Insert the set anchor and washer onto the suspension bolts for locking the Old building New building suspension bolts on the ceiling. •...
Page 7
CAUTION 1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 5mm. Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.
Page 8
• Drill the piping hole with 70mm dia, hole WALL Indoor Outdoor core drill. • Piping hole should be slightly slant to the outdoor side. 5~7mm INSULATION, OTHERS Insulate the joint and tubes completely. THERMAL INSULATION All thermal insulation must comply with local requirement. INDOOR UNIT Union for liquid pipe Thermal insulator for refrigerant pipe...
Page 9
Install the remote control box INSTALLATION OF REMOTE CONTROL BOX and cord correctly. POINT OF REMOTE CONTROLLER INSTALLATION • Although the room temperature sensor is in the indoor unit, the remote control box should be installed in such places away from direct sunlight and high humidity. INSTALLATION OF THE REMOTE CONTROL BOX ROUTING OF THE REMOTE CONTROL CORD •...
Page 10
Perform the work according to the Service REFRIGERANT PIPING Manual or Installation Guide. • Use two spanners when connect the refrigerant pipe to the unit. Flared connection (Union) • Make a bend with a radius as large as possible. Use a seemliness tube •...
Page 11
Perform the electrical wiring work according to ELECTRICAL WIRING the electrical wiring connection. • All wiring must comply with local Circuit Breaker requirements. Main power source • Select a power source that is capable of Switch box supplying the current required by the air conditioner.
3. Connecting Pipes to the Indoor Unit 3-1. Preparation of Piping Copper Main cause of gas leakage is defect in Slanted Uneven Rough tube 90° flaring work. Carry out correct flaring work in the following procedure. 1) Cut the pipes and the cable. Use the accessory piping kit or the pipes purchased locally.
Page 13
6) Pipe bending Annealed copper pipe with small diameter (ø6.35 or ø9.52) can be easily bent manually. In this case, secure large R(radius) for the bend section and gradually bend pipe. If annealed copper pipe is large in diameter (ø15.88 or ø19.05), bend pipe with bender. Use bender appropriate for the pipe diameter.
4. Connecting Pipes to the Outdoor Unit 1) Connecting the pipes to the Outdoor unit 1. Align the center of the pipings and sufficiently tighten the flare nut with fingers. 2. Finally, tighten the flare nut with torque wrench until the wrench clicks. •...
6. Connecting Cables between Indoor Unit and Outdoor Unit 1) Connecting cables to the Indoor Unit Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively 18K/24K Btu (220-240V~)
3) Connecting the cable to the Outdoor Unit Outdoor unit 1. Remove the Cover control from the unit Terminal block by loosening a screw. Connect the wires to the terminals on Cord Clamper the control board individually as following. 2. Secure the cable onto the control board Over 5mm with the holder (clamper).
4) Form the pipings 1. Wrap the connecting portion of indoor Seal a small opening unit with the Insulation material and around the pipings with gum type sealer. secure it with two Plastic Bands. (for the Drain hose right pipings) Taping •...
7. Air Purging of the Connecting Pipes and the Indoor Unit The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor. 1. Confirm that both the liquid side valve and the gas side valve are set to the closed position. 2.
8. Group Control It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to prevent overcurrent. Main PCB Indoor Unit 1 Indoor Unit 2 Indoor Unit 16 Terminal(Local Supply) Terminal(Local Supply) Terminal(Local Supply) Block Block Block Connector...
10. High-Static Motor Connection (For 48K/60K Model) 1. High-Static Motor Connection (For 48K Model) • If working condition of indoor unit is higher than that of standard static pressure (10mmAq) change the Indoor Control box Motor wire housing for standard motor housing for higher external static Pressure (15mmAq).
11. E.S.P.(External Static Pressure) Setting (1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. Without Zone System 1. Position V-H, F-H: • This position sets the maximum E.S.P as a default set. 2.
12. How to Set E.S.P? Procedure of RPM change: Ex) External Static pressure is 6mmAq for Model Name "LB-H1860 " • To protect the unit, compressor is designed to be off during E.S.P. setting. Push the "On/Off" button. The unit will start. AUTO SWING OPERATION SET TEMP...
Page 23
[Table. 1] Static Pressure(mmAq) Model Name Step(Hi/Med/Lo) Setting Value 16.5 CMM LB-H1860 14.5 CMM 13 CMM 18 CMM LB-H2460 16.5 CMM 14 CMM 32 CMM LB-G3660 29 CMM LB-G3680 26.5 CMM Note: 1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.