Connecting Synoloop Devices - Siemens Synova FC330A Manual

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

2.15

Connecting SynoLOOP devices

Note: for technical details see page 109
−> list order and type of all devices (field device list)
Base SO320A
OP320A
HI320A/322A
OH320A
APMK=1
+
+
+
+
micro terminals
front end
+
AI300
AI340
max. 2 response indicators
Loading capacity: addition of loading factor of all devices (APMK=...) shall not exceed the value of 128
1
2
3
4
+
+
application with explosion
hazard area see page 34
details see page 110
Input module
EB322A
APMK=1
EB322A
+
– + – +
L
M
4k75
32
Building Technologies
Fire Safety & Security Products
Smoke/heat detectors
Base SO320A
OP620A
HI62xA
OH620A
+
+
+
+
Response
indicator
AI340
In-/or output module
1)
CB320A or DC1192
–> set to
'SynoLOOP'
APMK=3
CB320A or DC1192
G
H
Q
R
V
+
+
Z
G
H
Q
R
V
or
24V
EOL22(Ex)
EOL1
collective
control
line
line
Output module
AB322A
1)
APMK=2
AB322A
30V/1A
– +
– +
Sockel SO620A
L
L
− + − + − +
+
SynoLOOP allows max. 128 devices
(cable max. 150W / 300nF)
MT320A
W
+
− +
W
MT320A
DC
details see page 111
1) max. 64 output
modules per
system FC330A
CO NN
Flame detectors
DF1191/92
–> set to 'SynoLOOP'
L
L
DFB1190
APMK=5
Manual call points
DM1133A
APMK=1
− + −
DM1133A
In-/and output module
ABI322A
1)
APMK=2
ABI322A
30V/1A
– + – +
– +
CO NC NO
L
M
+
rear end
4k75
Note:
Always both
in-/and output
must be used
free terminals
Z
Z
Z
1583_o_en_−−_2
08.2005