SELECT:
1. ENabling
(main menu)
2. DISabling
3. INFO polling
4. other functions
FUNCTIONS:
1. function
(4)
2. system TEST
3. printout
4. configuration
Service engineer
Erase configuration data
The option '4.4.4.3' sets all system parameters to their
country specific default value.
This means that the physical structure (device types, line
types etc.) and the logical structure (detector zone types,
allocated trigger to conTrol zones, all links) will be
changed and all user texts will be deleted.
Proceed as indicated to the right.
consequence of option 2 see on page 53
64
Building Technologies
Fire Safety & Security Products
Ê Details see page 71
Ë Details see page 101
Ì Details see page 115
CONFIGURATION:
1. user functions
(4.4)
2. user text
3. service functions
4. erase functions
Level SERVICE FUNCTIONS
> enter password?
hm: back to menu
Stop: end operating
SERVICE
1. addr. line −> CONNECT
level :
2. addr. line −> DISCON.
(4.4.3)
3. test AI−LED's ON/OFF
4. reconfigure addr. lines
5. horn/ctrl/RT −> OFF
6. TEST−alarm −> HORN
7. Visualizer ON/OFF
8. re−parametrise LON
Level SERVICE FUNCTIONS
> enter password?
hm: back to menu
Stop: end operating
ERASE data:
1. ERASE alarm counter
(4.4.4)
2. ERASE event memory
3. ERASE conf + sys data
4. ERASE element status
1. Go to menu 4.4.4
ERASE data:
(4.4.4)
2. Activate option 4.4.4.3
set USER DATA to DEFAULT?
> select?
hm: back to menu
3. Wait until the flash-write cycle is over
SYSTEM temporarily BLOCKED
> writing data in flash−EPROM
4. Press key 'RESET' (S1) on the main board K3X...
Autom. Restart of control panel with option 2
wait.. system START
POWER OFF > RESET line(s)
ready for CONFIGURATION
system on DEFAULT OPERATION
MON 2.6.03
(also via configuration tool SWE330A)
(also via configuration tool SWE330A)
Ê
direct setting user parameters
direct definition user texts
Ë
0033
connect addressable loop
disconnect addressable loop
for TEST LEDs
start automatic configuration of addr. lines
for COMMON disabling
to activate horn briefly with each det. TEST
alarm
enable / disable 'visualizer'
to start automatic configuration of LON-Bus 4
Ì
0033
(locked with switch 'S2')
(not locked)
see page 64
to erase 'non alarm' events
1. ERASE alarm counter
2. ERASE event memory
3. ERASE conf + sys data
4. ERASE element status
Stop: end operating
(50 sec.)
(1st startup)
12:10
Access level
0011
8642
4
4
Access level
0033
4
4
4
4
4
4
4
Access level
0033
4
4
4
1. no
2. yes
1583_o_en_−−_4
08.2005