Assigning device parameters
5.3 Configuration settings of the device
Save and restore the configuration file
You back up the configuration file of the device either directly on the device via USB or from
a PC via Remote configuration of several devices (Page 66).
The configuration file contains all device-specific configuration settings with the exception of
the background image and the touch calibration. You can back up the configuration file of a
device and reload it to several devices, for example:
● Use the "Save" button to back up the configuration file for the device to the connected
● Use the "Restore" button to reload the backed up configuration file from the connected
Note
Saving the configuration file
Configuration files of the older version V1.x are no longer supported. Back up the current
configuration file before and after each firmware update.
Restoring the configuration file
Only restore configuration files that were created on the device or with the Remote
Configuration Center. A configuration file may not be altered after backup, for example,
by means of an editor.
IP address conflicts
Do not restore configuration files with the same IP addresses on different devices.
Reassign the IP addresses.
Restore to factory settings
Restoring factory settings has the following effects:
● The default configuration file overwrites the configuration file. All connection data for the
● The administrator password for logon to the configuration settings is reset to the default
● The SSH password is reset to the default password, which has an effect on the SSH
● The calibration information is reset.
44
drive. To do this, you select a folder in the file system and close the dialog with "OK". The
configuration file is saved to the folder.
USB drive, for example, if the current configuration file has been inadvertently overwritten.
To do this, you select a configuration file from a file dialog and close the dialog with "OK".
The syntax within the configuration file is checked. If the syntax is free of errors, the
configuration file will be transferred to the device and the old configuration file will be
overwritten; otherwise a message will be output.
network, remote access and web browser is reset. The language and screen brightness,
the settings and position of the taskbar and on-screen keyboard, and the background
image are reset.
NOTICE
Data loss restoring the factory settings
Save the configuration file before you restore the factory settings and reload it
afterwards (see above).
administrator password "admin".
configuration service. Additional information is available in the section "Assigning a key
(Page 78)".
Industrial Thin Client ITC1200, ITC1500, ITC1900, ITC2200