Temperature display in
normal mode
Parameter
Standard display
No display
Setpoint
Room
temperature
Temperature display for
setpoint shift
Parameter
Setpoint display
Relative
Absolute
Note
116/140
Siemens
Building Technologies
In room units with an LCD, the temperature value to be displayed can be selected.
(Normal mode = setpoint without shift or reset shift).
LCD display
(Only room units with LCD).
Displays only the room operating mode and, if enabled, the
heating or cooling symbol.
Present temperature setpoint.
RAD01 = Heating setpoint.
CLC01 = Cooling setpoint.
CLC02 = Mean value between heating and cooling setpoint,
e.g. 22.5 °C as mean of SpH = 21 °C and SpC = 24 °C.
Present room temperature used as the input for the controller
(basic setting).
In room units with an LCD it is possible to define what is to be displayed in the event of
a setpoint shift.
LCD display
Basic setting: Relative.
(Only room units with LCD).
Shift value e.g. +3.0K (basic setting).
Present temperature setpoint, e.g. 23.0 °C.
RAD01 = Heating setpoint.
CLC01 = Cooling setpoint.
CLC02 = Mean value between heating and cooling setpoint.
If "Absolute setpoint shift" is selected, the LCD displays a scale that illustrates the shift
as it happens:
10385Z20
To reset the setpoint shift, refer to page
RXB (KNX) Applications library
Room unit
110
.
CLC and RAD description of functions for CC-02 CM110384en_03
HandyTool
*109
96
48
2
HandyTool
*110
0
4
28 Feb 2009