Siemens Desigo RXB Technical Manual page 132

Technical manual
Table of Contents

Advertisement

Existing Effective
room op. mode
Comfort
Precomfort
Economy
Protection.
52/140
Siemens
Building Technologies
The table below shows the effect of the Temporary Comfort mode on the Effective
room operating mode of the room controller.
Key:
1 means: "changes to 1 ".
1) Comfort mode is active for the predefined Temporary Comfort period (see page
103). The room controller then returns to Economy.
5.4.7
Effective room operating mode
Central
Local
Controller
Prio
S
1.
S
DI
1.
3.
S
S
3.
DI
S
3.
PPS2
3.
S
Effective room operating mode (output communication object)
Flags
Type
R W C T U
1 0 1 1 0 20.102
DPT_HVACMode
The resultant Effective room operating mode is also available as 4 digital
communication objects:
Effective room operating mode Comfort (output communication object)
Effective room operating mode Precomfort (output communication object)
Effective room operating mode Economy (output communication object)
Effective room operating mode Protection (output communication object)
Flags
Type
R W C T U
1 0 1 1 0 1.001
DPT_Switch
RXB (KNX) Applications library
Room operating modes
Temporary Comfort
mode
0 = Not used
1 = Trigger
1 = Trigger
1 = Trigger
The resultant Effective room operating mode is
available to the building automation and control
system in the following communication objects.
These are for display only and cannot be influenced.
Send heartbeat
Yes
Send heartbeat
Yes
CLC and RAD description of functions for CC-02 CM110384en_03
New Effective room
operating mode
No effect.
Comfort.
Comfort for Temporary
1)
Comfort period
.
Protection, unchanged.
States
1 = Comfort
2 = Precomfort
3 = Economy
4 = Protection
States
0 = Off
1 = On
28 Feb 2009