Two room groups for
Sport AG
Key
Room group definition
Important!
Settings on the control
unit
Siemens
Building Technologies
Let us know look at the floor plan for company Sport AG.
The company required separation of the rooms into two room groups or two
geographical zones (apartm) as follows:
– Conference room (room group 1).
– All other offices (room group 2).
The fan coil units equipped with RXB room controllers were entered in the floor plan,
and the addresses assigned accordingly:
x
x x
Conference
Room group 1
Conference
room
D: 114
G: 1.1.1
309
D: 113
G: 2.4.1
Sport Ltd
308
Office
D: 112
G: 2.3.1
D: 111
G: 2.2.1
x
x
x
x
Office
Raumgruppe 2
Room group 2
D = Device address, G = Geographical zone (Apartment . Room . Subzone).
On the KNX bus, several rooms are summarized in a room group via geographical
zone addressing. This address comprises three parts:
Geographical zone: Apartment . Room . Subzone
A geographical zone must be assigned:
– To each RXB room controller.
– To each room group of the RMB795 control station.
Here, all devices to be part of the same room group must have the same
apartment number.
The RMB795 control unit only allows for setting the room group, i.e. the geographical
zone (apartment).
RXB (KNX) Applications library
Select communications mode
x
x
x
x
x
SA EA
Enable
Setpoint prio
Relay
1
2
Q Q
RMB795
Office
307
D: 110
G: 2.1.1
x
x
x
x
SA EA
Enable
Setpoint prio
Relay
1
2
Q Q
CLC and RAD description of functions for CC-02 CM110384en_03
(e.g. 2 . 1 . 1)
25/140