ACS Service
HandyTool
Siemens
Building Technologies
Select the valve actuator type from Sequences :
Parameter
Short name
*060
Actuator type heating / cooling valve
Settings
STE71
1
STE72
2
STA71
3
STP71
4
STA72E
5
STP72E
6
With motorized actuators (conventional and bus actuators), third-party devices can
also be connected. The actuator running time can be adapted and an offset set
accordingly.
The offset considers the time between the electric pulse and the actual mechanic
movement of the actuator. This is especially important for fast running actuators.
For electromechanic actuators, the actuator running time can be adapted.
For fast actuators , select valve type "Motoric 3rd party devices ".
RXB (KNX) application library
Control sequences
SSA81
10
Motorized bus
SSB81
11
Electromech.
SQS81
12
third-party devices
Thermal third-party devices
SSC81
13
SSP81
14
Motorized third-party devices
FNC Description of functions for FC-10, FC-11, FC-12
Basic setting
STP72E ( FNC08: SSP81)
14
252
253
254
87/166
CM110385en_05