Siemens Desigo RXB Technical Manual page 141

Technical manual
Table of Contents

Advertisement

Room operating
mode schedule
Room with room unit
/ Auto Taste
am Raumgerät
Room 1
Effective room
operating mode
Room 1
Room with presence
detector
Presence
detector
Room 2
Effective room
operating mode
Room 2
Siemens
Building Technologies
The following conditions are specified:
• The building is in use from 06.00 to 20.00
(Protection from 20.00 to 06.00).
• Rooms 1 and 2 must be available from 08.00 to 18.00 (Precomfort).
• The occupant(s) of room 1 are working overtime. At 18.00, the room operating mode
changes to Economy , even if the room unit is set to Auto (1).
Comfort mode can now be reactivated with the Auto switch on the room unit (2).
Comfort remains active for the set Temporary Comfort mode period (see page 103).
In Protection mode, however, the Temporary Comfort period is also overridden and
the room operating mode changes to Protection (3).
• Room 2 is occupied in the evening beyond the building-in-use period (4). However,
at the end of the building-in-use period, the room operating mode still changes to
Protection. An alarm can be triggered if required.
Comfort
Precomfort
Economy
Protection
Auto
Comfort
Precomfort
Economy
Protection
Occupied
Unoccupied
Comfort
Precomfort
Economy
Protection
RXB (KNX) Applications library
Room operating modes
06:00
08:00
CLC and RAD description of functions for CC-02 CM110384en_03
10385D05
18:00
20:00
1)
3)
2)
1)
2)
3)
4)
4)
61/140
28 Feb 2009