528 Fault tracing
Code
Fault
(hex)
7584
LSU charge failed
8001
ULC underload fault
Programmable fault:
37.04 ULC underload
actions
8002
ULC overload fault
Programmable fault:
37.03 ULC overload
actions
80A0
AI supervision
Programmable fault:
12.03 AI supervision
function
80B0
Signal supervision
(Editable message text)
Programmable fault:
32.06 Supervision 1 action
80B1
Signal supervision 2
(Editable message text)
Programmable fault:
32.16 Supervision 2 action
80B2
Signal supervision 3
(Editable message text)
Programmable fault:
32.26 Supervision 3 action
9081
External fault 1
(Editable message text)
Programmable fault:
External event 1 source
31.02 External event 1
type
9082
External fault 2
(Editable message text)
Programmable fault:
External event 2 source
31.04 External event 2
type
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Cause
The supply unit was not ready
(ie. the main contactor/breaker
could not be closed) within
expected time.
Selected signal has fallen
below the user underload
curve.
Selected signal has exceeded
the user overload curve.
An analog signal is outside the
limits specified for the analog
input.
Fault generated by the signal
supervision 1 function.
Fault generated by the signal
supervision 2 function.
Fault generated by the signal
supervision 3 function.
Fault in external device 1.
31.01
Fault in external device 2.
31.03
What to do
Check that communication to the supply
unit has been activated by
options word
1.
Check setting of parameter
max charging
time.
Check that the supply unit is enabled,
allowed to start, and can be controlled by
the inverter unit (eg. not in local control
mode).
See
A8BF ULC underload warning
509).
See
A8BE ULC overload warning
508).
Check the auxiliary code (format XXXX
XYZZ). "Y" specifies the location of the
input (0: Control unit, 1: I/O extension
module 1, 2: I/O extension module 2, 3:
I/O extension module 3). "ZZ" specifies
the limit (01: AI1 under minimum, 02: AI1
above maximum, 03: AI2 under
minimum, 04: AI2 above maximum).
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group
Standard
AI.
Check the source of the fault (parameter
32.07 Supervision 1
signal).
Check the source of the fault (parameter
32.17 Supervision 2
signal).
Check the source of the fault (parameter
32.27 Supervision 3
signal).
Check the external device.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
95.20 HW
94.10 LSU
(page
(page
12
31.01
31.03