Product description 1 Product description The MFI is a Multi-Function Interface module that can be configured as reader interface or IO (input and output) module. It provides an interface between an (ACC AP) and up to eight OSDP readers and four doors.
Up to 8 Monitored inputs are used for Door position sensor inputs and REX inputs with MFI configured in Door Controller mode. These 8 inputs can be used as general input points with MFI configured in input-output controller mode. 8 relay outputs,...
12V, 200mA output Can be used for any load. OC 1, 2, 3 - Open Collector Outputs. Can be used to connect any custom load, that is, either powered from MFI board or powered externally. (Refer Section 9 Addendum) Enable/disable EOL for Reader communication port (J500).
Page 8
RS485 bus Connection to ACC AP - 2A and 2B is used for FLN communication. Note: 1A, 1B not used. Removal tamper Detects if the MFI is removed from the wall, provided that the screw is mounted. 12V output, max 500mA - shared with the reader when the power supply of 12V is used.
Scope of delivery 4 Scope of delivery 1 x MFI board with required resisters and jumpers. 1 x installation manual English. Restricted 9 | 18 A6V12068740 2020-09-07...
1. Remove the MFI from its carton and discard the packaging material. 2. Place the MFI against the surface to which it is to be affixed and mark the location of the mounting holes. We recommend mounting the MFI within a cabinet.
It is recommended that you wear a grounding strap while carrying out this procedure. 1. Connect OSDP readers to the appropriate READER port of MFI. Up to 8 OSDP readers can be connected. Each reader must be wired correctly. Refer Section 6.2 OSDP Reader wiring.
Reader connection via OSDP with or without encryption. The readers should be connected to the appropriate terminal blocks (A, B, -, +) of the READER port Mapping from MFI board to the Reader ports. Up to 8 OSDP readers can be daisy chained (from one reader to another) on the same connection.
Page 13
Connections and LEDs LEDs FLN Comm status LED H712 Orange The LED flashes to indicate communication between ACC-AP and MFI. Power status LED H713 Green Firmware status LED H711 Green LED blinking quickly: Firmware must be downloaded (device running bootloader).
Configuration and Firmware download 7 Configuration and Firmware download The MFI is configured using SiPass Configuration client, through the ACC-AP Controller AP01P, or using the ACC and FLN Field Service Tool. Refer to the and Device Installation Guide for more Information.
OC 2 OC 3 OC 1, OC 2, OC 3 points will be grounded, if they are activated from MFI to trigger current flow through the load(s). External power or one of MFI’s power output ports can be used for powering load on OC points.
Page 17
Addendum With multiple MFIs connected to ACC-AP, EOL must be enabled on ACC-AP and at the last MFI (on the line), if overall cable length between ACC-AP and last MFI exceeds 20m. Sample wiring between ACC-AP and MFIs: ACC-AP ACC-AP With readers connected to MFI, EOL resister must be enabled on MFI if cable length exceeds 20m.