hit counter script

Cycle Troubleshooting Guide - LG LB-E4880HL Service Manual

Ceiling duct air conditioner
Table of Contents

Advertisement

Cycle Troubleshooting Guide

Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Operating Current
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure
(Compared with
(Compared with
the normal value)
the normal value)
Higher
Lower
Notice :
1. The suction pressure is usually 4.5~6.0 kg/cm
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Temp. difference
Current
Temp. difference
Current
Temp. difference
Current
Temp. difference
Temperature
Defective compressor
High
Defective 4-way reverse valve
Excessive amount of
Normal
refrigerant
Insufficient amount of
Higher
refrigerant (Leakage)
Clogging
2
G at normal condition.
: approx. 0°C
: less than 80% of
rated current
: approx. 8°C
: less than 80% of
rated current
: less than 8°C
: over the rated
current
: over 8°C
Cause of Trouble
- 30 -
All amount of refrigerant leaked out
Check refrigeration cycle
Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
Excessive amount of refrigerant
Normal
Description
Current is low
High pressure does not quickly
rise at the beginning of
operation
Current is low
Current is low
LGE Internal Use Only

Advertisement

Table of Contents
loading

Table of Contents