3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
•
80010701-1403xxxx : Numeric sensor [NumericSensorElementName] going high (upper
non-critical) has asserted. (DIMM AB VR Temp)
This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
May also be shown as 800107011403xxxx or 0x800107011403xxxx
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - Temperature
SNMP Trap ID
12
CIM Information
Prefix: PLAT ID: 0490
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
•
80010701-1404xxxx : Numeric sensor [NumericSensorElementName] going high (upper
non-critical) has asserted. (DIMM CD VR Temp)
This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
May also be shown as 800107011404xxxx or 0x800107011404xxxx
Severity
Warning
Serviceable
Yes