hit counter script

Module Version "Ee@Industry Measurement Data Profile E0 / E1 / E2 / E3 - Siemens Simatic ET 200SP Manual

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

C.4
Module version "EE@Industry measurement data profile
E0 / E1 / E2 / E3"
User data of the module
The four versions according to EE@Industry use between 4 and 104 bytes of input user data
and 20 bytes of output user data. A dynamic switchover of the input user data is not
possible.
Structure of input user data
The structure of the input user data for the module versions according to the EE@Industry
standard is fixed and depends on the selected measurement data profile.
Table C- 6
Byte
0...3
4...7
8...11
Table C- 7
Byte
0...3
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
C.4 Module version "EE@Industry measurement data profile E0 / E1 / E2 / E3"
Measurement data profile E0
Allocation
Current L1
Current L2
Current L3
Measurement data profile E1
Allocation
Total active power L1L2L3
Data
Unit
Value range
type
REAL
1 A
0.0 ... 100000.0
REAL
1 A
0.0 ... 100000.0
REAL
1 A
0.0 ... 100000.0
Data
Unit
Value range
type
REAL
1 W
-3.0e+9 ... +3.0e+9
Module versions
Mea
sure
d
value
ID
7
8
9
Mea
sure
d
value
ID
34
203

Advertisement

Table of Contents
loading

Table of Contents