hit counter script

Siemens Simatic ET 200SP Manual page 223

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

User data variants
Basic variables phase-specific measurement (ID 157 or 9D
Table D- 21
Basic variables phase-specific measurement L2
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L2
4 ... 5
Voltage UL2-N
6 ... 7
Active power L2
8 ... 9
Reactive power Qtot L2
10 ... 11
Apparent power L2
12 ... 15
Active energy L2 total (inflow - outflow)
16 ... 19
Reactive energy L2 total (inflow - outflow)
20 ... 23
Apparent energy L2
24
Scaling current L2
25
Scaling active power L2
26
Scaling reactive power L2
27
Scaling apparent power L2
28
Scaling active energy L2 total (inflow - outflow)
29
Scaling reactive energy L2 total (inflow - outflow)
30
Scaling apparent energy L2
31
Power factor L2
222
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
)
H
Data
Unit
Value range
type
BYTE
-
157 (9D
BYTE
Bit string qq xx xx xx
UINT
1 mA
0 ... 65535
UINT
0.01 V
0 ... 65535
INT
1 W
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 VA
-27648 ... 27648
DINT
1 Wh
-2147483647...
+2147483647
DINT
1 varh
-2147483647...
+2147483647
UDINT
1 VAh
0 to 2147483647
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
0.01
0 ... 100
Manual, 07/2018, A5E42674880-AA
Meas-
ured
value
ID
)
-
H
-
66008
66002
66014
66023
66011
62215
62216
62214
-
-
-
-
-
-
-
66020

Advertisement