hit counter script

Siemens Simatic ET 200SP Manual page 172

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Meas-
Measured variables
ured
value
ID
62120
THD+N voltage L1
62121
THD+N current L1
62122
Fundamental voltage
L1
1
62123
Fundamental current
L1
1
62124
Fundamental reactive
power L1
3
62125
Fundamental apparent
power L1
3
62126
Fundamental active
power L1
3
62127
Fundamental cos φ
active factor L1
17
62130
Voltage L1 10-12 cy-
cles
1, 19
62131
Voltage L1 half cycle
16, 19
62133
Current L1 10-12 cy-
cles
1, 19
62134
Current L1 half cycle
16, 19
62136
Fundamental cos φ
active factor L1
17
62150
Max. THD+N voltage
L1
14
62151
Max. THD+N current
L1
14
62152
Max. fundamental
voltage L1
14
62153
Max. fundamental
current L1
14
62154
Max. fundamental
reactive power L1
62155
Max. fundamental
apparent power L1
62156
Max. fundamental
active power L1
62157
Max. fundamental cos
φ active factor L1
62160
Max. reactive power
Qtot L1
3
62170
Min. THD+N voltage
L1
14
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
Data
Unit
type
REAL
1%
13
REAL
1%
13
REAL
V
REAL
A
REAL
var
REAL
VA
REAL
W
REAL
-
REAL
V
REAL
V
1,
REAL
A
REAL
A
1,
SINT
0.01
REAL
1%
REAL
1%
REAL
V
REAL
A
REAL
var
14
REAL
VA
14
REAL
W
14
REAL
-
14
REAL
var
REAL
1%
Value range
1P
2W
0 % bis 100 %
0 % bis 100 %
0.0 ... 440.0
0.0 ... 100000.0
-3.0e+9 ... +3.0e+9
-3.0e+9 ... +3.0e+9
-3.0e+9 ... +3.0e+9
-1.0 ... 1.0
0.0 ... 760.0
0.0 ... 760.0
0.0 ... 100000.0
0.0 ... 100000.0
-100...100
0 % bis 100 %
0 % bis 100 %
0.0 ... 440.0
0.0 ... 100000.0
-3.0e+9 ... +3.0e+9
-3.0e+9 ... +3.0e+9
-3.0e+9 ... +3.0e+9
-1.0 ... 1.0
-3.0e+9 ... +3.0e+9
0 % bis 100 %
Measured variables
Connection type
2P
3x
3P
3P
3W
1P2W
4W
4W1
3P
3P
3P
3W
3W1
4WI
171