Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

User data variants
Basic variables phase-specific measurement (ID 159 or 9F
Table D- 19
Basic variables phase-specific measurement L1
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Voltage UL1-N
6 ... 7
Active power L1
8 ... 9
Reactive power Qtot L1
10 ... 11
Apparent power L1
12 ... 15
Active energy L1 total (inflow - outflow)
16 ... 19
Reactive energy L1 total (inflow - outflow)
20 ... 23
Apparent energy L1
24
Scaling current L1
25
Scaling active power L1
26
Scaling reactive power L1
27
Scaling apparent power L1
28
Scaling active energy L1 total (inflow - outflow)
29
Scaling reactive energy L1 total (inflow - outflow)
30
Scaling apparent energy L1
31
Power factor L1
220
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
)
H
Data
Unit
Value range
type
BYTE
-
159 (9FH)
BYTE
Bit
qq xx xx xx
string
UINT
1 mA
0 ... 65535
UINT
0.01 V
0 ... 65535
INT
1 W
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 VA
-27648 ... 27648
DINT
1 Wh
-2147483647...
+2147483647
DINT
1 varh
-2147483647...
+2147483647
UDINT
1 VAh
0 to 2147483647
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
0.01
0 ... 100
Manual, 07/2018, A5E42674880-AA
Meas-
ured
value
ID
-
-
66007
66001
66013
66022
66010
62115
62116
62114
-
-
-
-
-
-
-
66019