hit counter script

Siemens Simatic ET 200SP Manual page 210

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Apparent power L1L2L3 (ID 251 or FB
Table D- 5
Apparent power L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Current L2
6 ... 7
Current L3
8 ... 9
Apparent power L1
10 ... 11
Apparent power L2
12 ... 13
Apparent power L3
14 ... 15
Total apparent power L1L2L3
16 ... 19
Total apparent energy L1L2L3
20
Power factor L1
21
Power factor L2
22
Power factor L3
23
Total power factor L1L2L3
24
Scaling current L1
25
Scaling current L2
26
Scaling current L3
27
Scaling apparent power L1
28
Scaling apparent power L2
29
Scaling apparent power L3
30
Scaling apparent power L1L2L3
31
Scaling total apparent energy L1L2L3
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Data
Unit
Value range
type
BYTE
-
251 (FB
BYTE
Bit string
qq xx xx xx
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
INT
1 VA
-27648 ... 27648
INT
1 VA
-27648 ... 27648
INT
1 VA
-27648 ... 27648
INT
1 VA
-27648 ... 27648
DINT
1 VAh
0 to 2147483647
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
User data variants
Meas-
ured
value
ID
)
-
H
-
66007
66008
66009
66010
66011
66012
66036
224
66019
66020
66021
66037
-
-
-
-
-
-
-
-
209

Advertisement