The following table summarizes all the configurable parameters with STEP 7 (GSD file).
Table 13- 1
Parameters AI Energy Meter HF (GSD file)
Parameters
Hardware interrupt
Inputs
Diagnostics: Missing supply
voltage L+
Connection type
Voltage measuring range
Line frequency
Energy meter gate enabled
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
Value range
Disable
Enable
Disable
Enable
Disabled
1P2W - 1 phase, 2 conductors
3P4W - 3 phase current measurement, 4
conductors
3P4W1, 3 phases, 4 conductors, bal-
anced load
3P4W - 3 phases, 4 conductors
3x1P2W - 3 x 1 phase, 2 conductors
each
2P3W - 2 phases, 3 conductors
3P3W, 3 phases, 3 conductors
3P3W1, 3 phases, 3 conductors, bal-
anced load
100 V
110 V
115 V
120 V
127 V
190 V
200 V
208 V
220 V
230 V
240 V
277 V
50 Hz
60 Hz
Disable
Enable
13.1 Parameters
Default setting
Disable
Disable
3P4W - 3 phases, 4 con-
ductors
230 V
50 Hz
Disable
Parameters
Reconfigu-
ration in
RUN
No
Yes
Yes
Yes
Yes