Basic variables phase-specific measurement (ID 158 or 9E
Table D- 20
Single-phase measurement L1 with voltage scaling value
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Voltage UL1-N
6 ... 7
Active power L1
8 ... 9
Reactive power Qtot L1
10 ... 11
Apparent power L1
12 ... 15
Active energy L1 total (inflow - outflow)
16 ... 19
Reactive energy L1 total (inflow - outflow)
20 ... 23
Apparent energy L1
24
Scaling current L1
25
Scaling active power L1
26
Scaling reactive power L1
27
Scaling apparent power L1
28
Scaling active energy L1 total (inflow - outflow)
29
Scaling reactive energy L1 total (inflow - outflow)
30
Scaling apparent energy L1
31
Scaling voltage UL1-N
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
I
U
I
U
I
U
1
3
3
2
2
1
1
)
H
Data type Unit
Value range
BYTE
-
158 (9EH)
BYTE
Bit string
qq xx xx xx
UINT
1 mA
0 ... 65535
UINT
0.01 V
0 ... 65535
INT
1 W
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 VA
-27648 ... 27648
UDINT
1 Wh
0 ... 4294967295
UDINT
1 varh
0 ... 4294967295
UDINT
1 VAh
0 ... 4294967295
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
User data variants
Meas-
ured
value
ID
-
-
66007
66001
66013
66022
66010
62115
62116
62114
-
-
-
-
-
-
-
-
221