Total energy L1L2L3 (ID 249 or F9
Table D- 7
Total energy L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2
Reserved
3
Reserved
4 ... 7
Total active energy inflow L1L2L3
8 ... 11
Total active energy outflow L1L2L3
11 ... 15
Total reactive energy inflow L1L2L3
16 ... 19
Total reactive energy outflow L1L2L3
20 ... 23
Total apparent energy L1L2L3
24
Reserved
25
Scaling active energy, inflow
26
Scaling active energy, outflow
27
Scaling reactive energy, inflow
28
Scaling reactive energy, outflow
29
Scaling apparent energy
30
Reserved
31
Total power factor L1L2L3
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Data
Unit
Value range
type
BYTE
-
249 (F9
BYTE
Bit
qq xx xx xx
string
BYTE
-
-
BYTE
-
-
UDINT
1 Wh
0 to 2147483647
UDINT
1 Wh
0 to 2147483647
UDINT
1 varh
0 to 2147483647
UDINT
1 varh
0 to 2147483647
UDINT
1 VAh
0 to 2147483647
BYTE
-
-
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
BYTE
-
-
USINT
0.01
0 ... 100
User data variants
Meas-
ured
value
ID
)
-
H
-
-
-
210
211
212
213
214
-
-
-
-
-
-
-
66037
211