Measured value data records
E.12 Measured value data record of user-defined data record (DS 151)
Byte
Measured variable
88...91
Power quality analysis - Qualifier
92...103
Current module time
Energy counters count periodically - counter overflow at:
1
Bit 0 = 1: Active energy inflow L1
Bit 1 = 1: Active energy outflow L1
Bit 2 = 1: Reactive energy inflow L1
Bit 3 = 1: Reactive energy outflow L1
Bit 4 = 1: Apparent energy L1
Bit 5 = 1: Active energy inflow L2
Bit 6 = 1: Active energy outflow L2
Bit 7 = 1: Reactive energy inflow L2
Bit 8 = 1: Reactive energy outflow L2
Bit 9 = 1: Apparent energy L2
Bit 10 = 1: Active energy inflow L3
Bit 11 = 1: Active energy outflow L3
Bit 12 = 1: Reactive energy inflow L3
Bit 13 = 1: Reactive energy outflow L3
Bit 14 = 1: Apparent energy L3
Bit 15: Reserved
E.12
Measured value data record of user-defined data record (DS 151)
The length and structure of the data record DS 151 depends on the parameter assignment of
the data record DS 135 (Page 160).
Byte
Measured variable
0
Version
1
Number of measured values
2
Measured value 1 corresponding to measured
value ID 1 in DS135
3
Measured value 2 corresponding to measured
value ID 2 in DS135
...
...
... m
Measured value n corresponding to measured
value ID n in DS135
258
Data
Unit
type
UDINT
Bit
string
PNI-
sec
OTime
Data
Unit
type
UINT8
-
UINT8
-
Depending on the corresponding measured value ID
Depending on the corresponding measured value ID
Depending on the corresponding measured value ID
Depending on the corresponding measured value ID
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Value range
-
-
Default
0
0
Manual, 07/2018, A5E42674880-AA
Meas-
ured
value
ID
65496
65497
Meas-
ured
value
ID
-
-