COMMISSIONING
266
Starting Operation flow chart
START
Operate the unit in heating mode.
Does Test operation start?
Yes
Is cold water discharged for
more than 3 minutes ?
No
Is there any temperature
difference between intake and
discharged water?
Yes
Is hot water discharged ?
Yes
Normal

Airborne Noise Emission

The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels.
Whilst there is a correlation between the emission and exposure levels, this cannot be used
reliably to determine whether or not further precautions are required.
Factor that influence the actual level of exposure of the workforce include the characteristics of
the work room and the other sources of noise, i.e. the number of equipment and other adjacent
processes and the length of time for which an operator exposed to the noise.
Also, the permissible exposure level can vary from country to country.
This information, however, will enable the user of the equipment to make a better evaluation of
the hazard and risk.
No
Check whether the power cable and
communication cable are completely connected
Yes
* Check the load (In/Out Temp.)
* Check pipe length and amount of
refrigerant
* Check for abnormal sound in
No
outdoor unit (comp.,Fan, others )
* Refer to Troubleshooting Guide
No