Water pump Capacity
The water pump us variable type which is capable to change flow rate, so it may be required to
change default water pump capacity in case of noise by water flow. In most case, however, it is
strongly recommended to set capacity as Maximum.
NOTE
• To secure enough water flow rate, do not set water pump capacity as Minimum.
It can lead unexpected flow rate error CH14.
Pressure Drop
NOTE
When installing the product, install additional pump in consideration of the pressure loss and
pump performance. If flow rate is low, overloading of product can occur
(For GRUNDFOS Water Pump)
Capacity
Rated flow-rate
[kW]
[LPM(m
16
46.0 (2.8)
14
40.25 (2.4)
12
34.5 (2.1)
9
25.87 (1.5)
7
20.12 (1.2)
5
15.8 (0.9)
(For OH SUNG Water Pump)
Capacity
Rated flow-rate
[kW]
[LPM(m
16
46.0 (2.8)
14
40.3 (2.4)
12
34.5 (2.1)
9
25.9 (1.5)
7
20.1 (1.2)
5
15.8 (0.9)
Pump Head [m]
3
/h)]
(At rated flow rate)
8.3
9.3
9.8
6.1
7.3
7.5
Pump Head [m]
3
/h)]
(At rated flow rate)
8.5
9.1
9.7
10.3
10.7
10.9
INSTALLATION
Product pressure
drop [m]
Serviceable Head
(Plate heat
exchanger)
1.4
1.1
0.8
0.4
0.3
0.2
Product pressure
drop [m]
Serviceable Head
(Plate heat
exchanger)
1.4
1.1
0.8
0.4
0.3
0.2
67
[m]
6.9
8.2
9.0
5.7
7.0
7.3
[m]
7.1
8.0
8.9
9.9
10.4
10.7